Product Features

  • VRLA (valve-regulated lead-acid) battery
  • Maintenance-free; with AGM absorbed glass mat separator technology, gas recombination efficiency can reach 99%
  • Constructed from pure lead with proprietary elements
  • Developed for high-rate UPS and float standby power applications
  • Manufactured in accordance with IEC 60896-21/22:2004 and recognized under UL1989 (MH14533)

Application Scenarios

  • Long-duration UPS backup for data centers
  • Long-duration standby power for large computer rooms
  • Backup duty under long-duration discharge in industrial UPS applications
  • Long-duration backup applications for financial systems
  • Long-duration standby power support for telecom hubs
  • Long-duration UPS applications for medical centers

Product parameters

  • Model:XPL4200
  • Voltage:12 Vdc
  • Nominal Capacity:4200W @5min-rate
  • Watts per Cell:979.83 (30-Sec 1.67 VPC @ 25°C)
  • Watts per Cell:660.50 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:370.17 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:35.00 A
  • Max. Discharge Current:900 A
  • Short Circuit Current:2616 A
  • Internal Resistance:3.22 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
  • Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:28.20 / 62.17 kg / lb.
  • Length (L):261.0±2.5 / 10.28±0.10 mm / in
  • Width (W):168.5±2.0 / 6.63±0.08 mm / in
  • Height (H):213.5±2.5 / 8.41±0.10 mm / in
  • Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

The XPL4200 belongs to CSB's XPL series; its official application area is data center UPS (uninterruptible power supply), and this high-capacity pure lead VRLA series is intended for long-duration standby applications that require large batteries. As a 12V valve-regulated sealed lead-acid battery, it uses absorbent glass mat (AGM) technology, can achieve 99% gas recombination efficiency, and is maintenance-free; its pure lead construction and proprietary element design allow it to be used in high-rate UPS and float standby power supplies. In addition, the battery complies with IEC 60896-21/22:2004 and is UL1989 recognized (MH14533). For electrical performance, starting with current and internal resistance: XPL4200 maximum charge current is 35.00 A, maximum discharge current is 900 A, short-circuit current is 2616 A, and internal resistance is 3.22 mΩ. Nominal capacity is 4200W @5min-rate (9.60V per PCS @ 25°C). As for W/cell power, 30 seconds (1.67 VPC @ 25°C) reaches 979.83 W/cell, 5 minutes (1.67 VPC @ 25°C) is 660.50 W/cell, and 15 minutes (1.67 VPC @ 25°C) is 370.17 W/cell. Mechanical and installation parameters are as follows: Weight 28.20 kg (62.17 lb), length 261.0±2.5 mm, width 168.5±2.0 mm, height 213.5±2.5 mm. Case material is PP (UL 94-HB); a flame-retardant (94-V0) version is also available on request. Terminal type is I2 thread lead alloy terminal to accept M6 bolt; terminal torque is 51.7±10.3 Kgf∙cm / 44.9±9.0 Lbf∙in / 5.1±1.0 N∙m. At 25°C, the XPL4200 has a design life of up to 10 years in standby service and meets the Eurobat (20°C) >12-year Very Long Life standard. Its nominal temperature is 25°C, discharge range is -15°C to 50°C, and charge/storage range is -15°C to 40°C. At 25°C, float voltage is 13.5 - 13.8 Vdc/battery, and equalization voltage is 14.4 - 15.0 Vdc/battery. Self-discharge is less than 10% after 90 days at 25°C; storage time is up to 6 months, and the storage period can be extended if equalization charging is performed every 10 months. Fully charge before use; if storage temperature is above 25°C, recharge sooner.