HRL12200W Battery — CSB Valve-Regulated Sealed Lead-Acid Type 12V 200W
For data center UPS float standby power scenarios, the HRL series is designed with high-rate pure lead; HRL12200W is a CSB 12V valve-regulated sealed lead-acid battery, with 15-minute rate 200W, 5-minute rate 385W/cell.
Taobao store
WeChat procurement
Product Features
- VRLA (Valve-Regulated Lead-Acid) Battery
- No routine maintenance required; with AGM (Absorbent Glass Mat) technology, gas recombination efficiency up to 99%
- Based on a pure lead structure and incorporating proprietary elements
- Developed for float-charge standby power and high-rate UPS applications
- Manufacturing process complies with IEC 60896-21/22:2004 standard and has also received UL1989 recognition (MH14533)
Application Scenarios
- UPS backup power for large data centers
- High-voltage DC backup for cloud computing centers
- Uninterruptible power supply for financial trading systems
- UPS emergency backup for communication hubs
- High-power UPS backup for industrial automation
- UPS backup for rail transit signaling
Product parameters
- Model:HRL12200W
- Voltage:12 Vdc
- Nominal Capacity:200W @15min-rate
- Watts per Cell:385 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:218 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:20.0 A
- Max. Discharge Current:400 A
- Short Circuit Current:1509 A
- Internal Resistance:5.50 mΩ
- Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
- Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.10±1.0 N·m
- Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:17.30 / 38.13 kg / lb.
- Length (L):228.0±2.5 / 8.98±0.10 mm / in
- Width (W):138.4±1.5 / 5.45±0.06 mm / in
- Height (H):206.3±2.5 / 8.12±0.10 mm / in
- Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
The HRL series is positioned in the UPS pure lead battery market, with core features of long life and high rate. Target scenarios cover high-power data centers and UPS loads; the official application direction focuses on data center uninterruptible power supplies, covering high-rate UPS and float standby power requirements.
CSB's HRL12200W belongs to the HRL series and is a valve-regulated sealed lead-acid battery with top terminals using a 6V plus 12V structure. Its AGM absorbent glass mat technology allows gas recombination efficiency to reach up to 99%, requiring no maintenance during operation. The rated voltage is 12 Vdc; at 1.67 VPC, 25°C, the 15-minute rate nominal capacity is 200W. At 5-minute rate, 1.67 VPC, 25°C, the cell power is 385 W/cell; under the same conditions but at 15-minute rate, the cell power is 218 W/cell.
For electrical limits, the HRL12200W has a maximum charge current of 20.0 A, maximum discharge current of 400 A, short-circuit current of 1509 A, and internal resistance of 5.50 mΩ. At 25°C, the float charge voltage range is 13.5 to 13.8 Vdc/battery, and the equalization charge voltage range is 14.4 to 15.0 Vdc/battery. After 90 days of storage, self-discharge remains below 10%; at 25°C, it can be stored for up to 6 months; it must be fully charged before being put into operation. If storage temperature is higher than 25°C, supplementary charging should be advanced accordingly.
The terminal uses an I2 threaded lead alloy structure, accepts M6 bolts, and the terminal torque is 51.7±10.3 Kgf·cm or 44.9±9.0 Lbf·in or 5.10±1.0 N·m. The case material is PP (UL 94-HB), and a flame-retardant 94-V0 version can also be supplied upon request. Length, width, and height are 228.0±2.5 mm, 138.4±1.5 mm, 206.3±2.5 mm respectively, and weight is 17.30 kg.
When in float charge state at 25°C, the HRL12200W design life can reach 10 years; measured by Eurobat (20°C), it exceeds 12 years, classified as a very long life grade. Nominal temperature is 25°C, discharge range is -15°C to 50°C, and charge and storage range is -15°C to 40°C.
Manufacturing standard is IEC 60896-21/22:2004; it also has UL1989 recognition (MH14533). Through the combination of pure lead construction and proprietary formulation elements, the battery can still maintain stable performance under float standby and high-rate discharge requirements.