CSB HRL12110W 12V HRL Series Valve-Regulated Sealed Lead-Acid Battery
For high-rate float standby requirements, the CSB HRL12110W can be used in scenarios such as data center UPS. It belongs to the HRL series, has a voltage of 12V, is a valve-regulated sealed lead-acid battery, and is constructed with AGM and pure lead. In terms of parameters, the 5-minute rate is 211 W/cell, the 15-minute rate nominal capacity is 110W; the maximum float design life is 10 years.
Taobao store
WeChat procurement
Product Features
- Belongs to the Valve-Regulated Lead-Acid (VRLA) battery category
- Uses AGM (Absorbent Glass Mat) technology to achieve up to 99% gas recombination efficiency and is maintenance-free
- Based on a pure lead construction with proprietary elements added
- Designed for high-rate UPS and float standby power applications
- Manufacturing process complies with IEC 61056-1/2:2012 and has obtained UL1989 recognition (MH14533)
Application Scenarios
- UPS backup: large data centers
- High-voltage DC backup: cloud computing centers
- Uninterruptible power supply: financial trading systems
- UPS emergency support: communications hubs
- UPS high-power backup: industrial automation
- UPS backup: rail transit signaling
Product parameters
- Model:HRL12110W
- Voltage:12 Vdc
- Nominal Capacity:110W @15min-rate
- Watts per Cell:211 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:111 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:11.0 A
- Max. Discharge Current:225 A
- Short Circuit Current:884 A
- Internal Resistance:8.10 mΩ
- Terminal Type:I1 thread lead alloy terminal to accept M5 bolt
- Terminal Torque:30.4±6.1 Kgf·cm / 26.4±5.3 Lbf·in / 3.0±0.6 N·m
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:9.90 / 21.82 kg / lb.
- Length (L):166.0±2.0 / 6.54±0.08 mm / in
- Width (W):125.0±1.5 / 4.92±0.06 mm / in
- Height (H):175.0±2.0 / 6.89±0.08 mm / in
- Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): 10-12 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
CSB HRL12110W is one model in the HRL series; this series covers 6V and 12V top-terminal VRLA-AGM products, while this model's rated voltage is 12 Vdc. The HRL series is positioned as a long-life, high-rate pure lead battery, designed for high-power-demand and demanding data center and UPS loads, and its official application area is data center uninterruptible power supply. Under 1.67 VPC at 25°C, its 15-minute rate nominal capacity is 110W; at the 5-minute rate the power is 211 W/cell, and at the 15-minute rate the power is 111 W/cell.
In construction, the HRL12110W is based on a valve-regulated sealed lead-acid design and incorporates absorbent glass mat AGM technology, with gas recombination efficiency up to 99%, so it is maintenance-free; its pure lead construction combined with a proprietary element formulation can be used for high-rate UPS float standby power. Manufacturing standards follow IEC 61056-1/2:2012, and it is UL1989 recognized (MH14533). The case uses ABS (UL 94-HB); a flame-retardant 94-V0 version is available upon request.
Dimensions and terminal information are: weight 9.90 kg (21.82 lb); length 166.0±2.0 mm, width 125.0±1.5 mm, height 175.0±2.0 mm. The battery is equipped with I1 threaded lead alloy terminals and can accept M5 bolts; terminal torque is 30.4±6.1 Kgf·cm, 26.4±5.3 Lbf·in, or 3.0±0.6 N·m.
In terms of electrical parameters, the HRL12110W has a maximum charge current of 11.0 A, maximum discharge current of 225 A, short-circuit current of 884 A, and internal resistance of 8.10 mΩ. At 25°C, float voltage is 13.5 to 13.8 Vdc/battery; equalization voltage is 14.4 to 15.0 Vdc/battery. Regarding self-discharge, after 90 days at 25°C it is less than 10%, and storage can last up to 6 months; fully charge before use; when storage temperature is above 25°C, supplementary charging should be carried out sooner. In terms of temperature, nominal temperature is 25°C (77°F); discharge range is -15°C to 50°C (5°F to 122°F); charge and storage range is -15°C to 40°C (5°F to 104°F). Under 25°C float standby service, design life is up to 10 years; Eurobat (20°C) standard commercial life is 10 to 12 years.