CSB HR1232W Battery: 12V 32W, Valve-Regulated Sealed Lead-Acid
In float-charge standby power scenarios such as data center UPS, the HR series 12V valve-regulated sealed lead-acid battery CSB HR1232W can be used; it is made with pure lead and AGM technology, with a nominal capacity of 32W at the 15-minute rate.
Taobao store
WeChat procurement
Product Features
- VRLA valve-regulated lead-acid battery
- Uses AGM absorbent glass mat separator technology, maintenance-free, enabling efficient gas recombination with a recombination rate of up to 99%
- Pure lead construction with proprietary elements
- Specially designed for high-rate UPS and float-charge standby power applications
- Manufacturing process complies with IEC 61056-1/2:2012 standard and is UL1989 recognized (MH14533)
Application Scenarios
- Small and medium-sized data centers, with backup power provided by UPS
- Server cabinets, backed by uninterruptible power supply
- Network rooms, backed by emergency power supply
- Medical imaging equipment, with UPS serving as backup power
- Industrial control scenarios, with fast UPS discharge
- Precision instruments in laboratories, with backup power providing supply
Product parameters
- Model:HR1232W
- Voltage:12 Vdc
- Nominal Capacity:32W @15min-rate
- Watts per Cell:66.1 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:32.0 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:3.20 A
- Max. Discharge Current:130 A
- Short Circuit Current:335 A
- Internal Resistance:22.7 mΩ
- Terminal Type:F2 terminal (Faston Tab 250)
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:2.34 / 5.16 kg / lb.
- Length (L):150.9±2.0 / 5.94±0.08 mm / in
- Width (W):64.8±1.0 / 2.55±0.04 mm / in
- Height (H):98.6±1.0 / 3.88±0.04 mm / in
- Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
For UPS with lower output power, fast-discharge standby scenarios, and the officially listed data center uninterruptible power supply field, the CSB HR1232W is classified in the HR series. It is a 12V top-terminal valve-regulated sealed lead-acid battery, with a body constructed from pure lead and a proprietary element formulation; combined with absorbed glass mat (AGM) technology, gas recombination efficiency can reach up to 99%, and it has an overall maintenance-free design. This series focuses on high-rate discharge.
Electrically, the HR1232W has a nominal voltage of 12 Vdc; at 25°C and 1.67 VPC, its nominal capacity is 32W at the 15-minute rate. The battery's 5-minute rate reaches 66.1 W/cell at 25°C and 1.67 VPC, and its 15-minute rate is 32.0 W/cell. Maximum charge current is 3.20 A, maximum discharge current is 130 A, short-circuit current is 335 A, and internal resistance is 22.7 mΩ.
Charge parameters and temperature limits are as follows: at 25°C, float charge voltage must be 13.5 to 13.8 Vdc/battery, and equalization charge voltage is 14.4 to 15.0 Vdc/battery. Nominal operating temperature is 25°C; discharge temperature ranges from -15°C to 50°C, while charge and storage temperatures range from -15°C to 40°C. At 25°C, self-discharge is below 10% after 90 days, and storage time is up to 6 months; fully charge before reuse, and if storage temperature is above 25°C, charge ahead of time.
Dimensions: the HR1232W is 150.9±2.0 mm (L) × 64.8±1.0 mm (W) × 98.6±1.0 mm (H), weighs 2.34 kg, and uses F2-Faston Tab250 terminals. The case is made of ABS and meets UL 94-HB; a flame-retardant 94-V0 version is also available on request. When used on float charge at 25°C, design life is up to 5 years, and commercial life under the Eurobat 20°C standard is 3 to 5 years.
The product is manufactured to IEC 61056-1/2:2012 and is UL1989 recognized, recognition number MH14533. Because it features high-rate discharge and is intended for float-charge standby, the HR1232W can be used in fast-discharge backup applications such as data center UPS, and can be kept on continuous float charge at 25°C at the above float voltage.