HR1224W CSB 12V 24W Valve-Regulated Sealed Lead-Acid Battery
In float standby power applications, such as data center UPS, the CSB HR1224W can provide backup power. This battery is a 12V valve-regulated sealed lead-acid type, combining pure lead construction with AGM technology, and has a nominal capacity of 24W at the 15-minute rate.
Taobao store
WeChat procurement
Product Features
- Battery type is Valve Regulated Lead Acid (VRLA)
- Maintenance-free; gas recombination efficiency up to 99%, achieved through Absorbent Glass Mat (AGM) technology
- Constructed with pure lead and proprietary elements
- Developed for high-rate UPS and float standby power applications
- Manufactured in accordance with IEC 61056-1/2:2012 and is recognized under UL1989 (MH14533)
Application Scenarios
- UPS backup power for small and medium-sized data centers
- Uninterruptible power supply for server cabinets
- Emergency power backup covers network equipment rooms
- UPS backup power for medical imaging equipment
- UPS rapid discharge for industrial control
- Backup power supports laboratory precision instruments
Product parameters
- Model:HR1224W
- Voltage:12 Vdc
- Nominal Capacity:24W @15min-rate
- Watts per Cell:54.8 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:27.0 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:2.40 A
- Max. Discharge Current:130 A
- Short Circuit Current:260 A
- Internal Resistance:20.6 mΩ
- Terminal Type:F2 terminal (Faston Tab 250)
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:1.95 / 4.30 kg / lb.
- Length (L):150.9±2.0 / 5.94±0.08 mm / in
- Width (W):51.0±1.0 / 2.01±0.04 mm / in
- Height (H):98.6±1.0 / 3.89±0.04 mm / in
- Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
- Note:F1 terminal is available; Max Discharge Current = 100 A
Product details
HR1224W is a product in CSB's HR series and belongs to the 12V Top Terminal valve-regulated sealed lead-acid battery category. It uses an absorbent glass mat separator, also known as AGM technology, with gas recombination efficiency of up to 99%, and normally requires no maintenance. This series is positioned as a high-rate discharge pure lead battery series, targeting UPS with lower output power and fast-discharge backup scenarios; the officially listed application is data center uninterruptible power supplies.
In terms of specifications, HR1224W has a voltage of 12 Vdc; at 1.67 VPC and 25°C, the nominal capacity is 24W @15min-rate. On the same 1.67 VPC and 25°C basis, the 5-minute rate power reaches 54.8 W/cell, and the 15-minute rate power is 27.0 W/cell. The battery's maximum charging current is 2.40 A, short-circuit current is 260 A, and internal resistance is 20.6 mΩ. The terminal type is F2-Faston Tab250.
In terms of dimensions, HR1224W is 150.9±2.0 mm long, 51.0±1.0 mm wide, and 98.6±1.0 mm high, and weighs 1.95 kg. The case uses ABS material and meets UL 94-HB flame retardant requirements; a 94-V0 flame retardant case can also be provided on request. For design life, it can last up to 5 years in float standby service at 25°C, and 3 to 5 years under the Eurobat standard at 20°C.
Charging and temperature conditions are as follows: at 25°C, the float charging voltage is 13.5 to 13.8 Vdc/battery, and the equalization charging voltage is 14.4 to 15.0 Vdc/battery. The nominal operating temperature is 25°C; discharge is allowed from -15°C to 50°C, and charging and storage are allowed from -15°C to 40°C. For self-discharge, after 90 days in a 25°C environment, capacity loss is less than 10%; it can be stored for up to 6 months and should be fully charged before use; when storage temperature exceeds 25°C, it must be recharged earlier.
The product is manufactured in accordance with IEC 61056-1/2:2012 and has obtained UL1989 Recognized (MH14533). With its pure lead construction and high-rate discharge capability, it is suitable for float service scenarios such as data center UPS that require fast-discharge backup.