Product Features

  • Battery type is Valve Regulated Lead Acid (VRLA)
  • Maintenance-free; gas recombination efficiency up to 99%, achieved through Absorbent Glass Mat (AGM) technology
  • Constructed with pure lead and proprietary elements
  • Developed for high-rate UPS and float standby power applications
  • Manufactured in accordance with IEC 61056-1/2:2012 and is recognized under UL1989 (MH14533)

Application Scenarios

  • UPS backup power for small and medium-sized data centers
  • Uninterruptible power supply for server cabinets
  • Emergency power backup covers network equipment rooms
  • UPS backup power for medical imaging equipment
  • UPS rapid discharge for industrial control
  • Backup power supports laboratory precision instruments

Product parameters

  • Model:HR1224W
  • Voltage:12 Vdc
  • Nominal Capacity:24W @15min-rate
  • Watts per Cell:54.8 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:27.0 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:2.40 A
  • Max. Discharge Current:130 A
  • Short Circuit Current:260 A
  • Internal Resistance:20.6 mΩ
  • Terminal Type:F2 terminal (Faston Tab 250)
  • Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:1.95 / 4.30 kg / lb.
  • Length (L):150.9±2.0 / 5.94±0.08 mm / in
  • Width (W):51.0±1.0 / 2.01±0.04 mm / in
  • Height (H):98.6±1.0 / 3.89±0.04 mm / in
  • Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
  • Note:F1 terminal is available; Max Discharge Current = 100 A

Product details

HR1224W is a product in CSB's HR series and belongs to the 12V Top Terminal valve-regulated sealed lead-acid battery category. It uses an absorbent glass mat separator, also known as AGM technology, with gas recombination efficiency of up to 99%, and normally requires no maintenance. This series is positioned as a high-rate discharge pure lead battery series, targeting UPS with lower output power and fast-discharge backup scenarios; the officially listed application is data center uninterruptible power supplies. In terms of specifications, HR1224W has a voltage of 12 Vdc; at 1.67 VPC and 25°C, the nominal capacity is 24W @15min-rate. On the same 1.67 VPC and 25°C basis, the 5-minute rate power reaches 54.8 W/cell, and the 15-minute rate power is 27.0 W/cell. The battery's maximum charging current is 2.40 A, short-circuit current is 260 A, and internal resistance is 20.6 mΩ. The terminal type is F2-Faston Tab250. In terms of dimensions, HR1224W is 150.9±2.0 mm long, 51.0±1.0 mm wide, and 98.6±1.0 mm high, and weighs 1.95 kg. The case uses ABS material and meets UL 94-HB flame retardant requirements; a 94-V0 flame retardant case can also be provided on request. For design life, it can last up to 5 years in float standby service at 25°C, and 3 to 5 years under the Eurobat standard at 20°C. Charging and temperature conditions are as follows: at 25°C, the float charging voltage is 13.5 to 13.8 Vdc/battery, and the equalization charging voltage is 14.4 to 15.0 Vdc/battery. The nominal operating temperature is 25°C; discharge is allowed from -15°C to 50°C, and charging and storage are allowed from -15°C to 40°C. For self-discharge, after 90 days in a 25°C environment, capacity loss is less than 10%; it can be stored for up to 6 months and should be fully charged before use; when storage temperature exceeds 25°C, it must be recharged earlier. The product is manufactured in accordance with IEC 61056-1/2:2012 and has obtained UL1989 Recognized (MH14533). With its pure lead construction and high-rate discharge capability, it is suitable for float service scenarios such as data center UPS that require fast-discharge backup.
link
Go to purchase
Telephone
13775032303
email
powercube@foxmail.com
wechat
wechat