HR1224W csb battery 12V Suitable for UPS backup power for small and medium-sized data centers, Uninterruptible power supply for server cabinets, Emergency power backup covers network equipment rooms
In float standby power applications, such as data center UPS, the CSB HR1224W can provide backup power. This battery is a 12V valve-regulated sealed lead-acid type, combining pure lead construction with AGM technology, and has a nominal capacity of 24W at the 15-minute rate.
Taobao store
WeChat procurement
Product Features
- Battery type is Valve Regulated Lead Acid (VRLA)
- Maintenance-free; gas recombination efficiency up to 99%, achieved through Absorbent Glass Mat (AGM) technology
- Constructed with pure lead and proprietary elements
- Developed for high-rate UPS and float standby power applications
- Manufactured in accordance with IEC 61056-1/2:2012 and is recognized under UL1989 (MH14533)
Application Scenarios
- UPS backup power for small and medium-sized data centers
- Uninterruptible power supply for server cabinets
- Emergency power backup covers network equipment rooms
- UPS backup power for medical imaging equipment
- UPS rapid discharge for industrial control
- Backup power supports laboratory precision instruments
Product parameters
- Model:HR1224W
- Voltage:12 Vdc
- Nominal Capacity:24W @15min-rate
- Watts per Cell:54.8 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:27.0 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:2.40 A
- Max. Discharge Current:130 A
- Short Circuit Current:260 A
- Internal Resistance:20.6 mΩ
- Terminal Type:F2 terminal (Faston Tab 250)
- Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:1.95 / 4.30 kg / lb.
- Length (L):150.9±2.0 / 5.94±0.08 mm / in
- Width (W):51.0±1.0 / 2.01±0.04 mm / in
- Height (H):98.6±1.0 / 3.89±0.04 mm / in
- Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
- Note:F1 terminal is available; Max Discharge Current = 100 A
Product details
HR1224W is a product in CSB's HR series and belongs to the 12V Top Terminal valve-regulated sealed lead-acid battery category. It uses an absorbent glass mat separator, also known as AGM technology, with gas recombination efficiency of up to 99%, and normally requires no maintenance. This series is positioned as a high-rate discharge pure lead battery series, targeting UPS with lower output power and fast-discharge backup scenarios; the officially listed application is data center uninterruptible power supplies.
In terms of specifications, HR1224W has a voltage of 12 Vdc; at 1.67 VPC and 25°C, the nominal capacity is 24W @15min-rate. On the same 1.67 VPC and 25°C basis, the 5-minute rate power reaches 54.8 W/cell, and the 15-minute rate power is 27.0 W/cell. The battery's maximum charging current is 2.40 A, short-circuit current is 260 A, and internal resistance is 20.6 mΩ. The terminal type is F2-Faston Tab250.
In terms of dimensions, HR1224W is 150.9±2.0 mm long, 51.0±1.0 mm wide, and 98.6±1.0 mm high, and weighs 1.95 kg. The case uses ABS material and meets UL 94-HB flame retardant requirements; a 94-V0 flame retardant case can also be provided on request. For design life, it can last up to 5 years in float standby service at 25°C, and 3 to 5 years under the Eurobat standard at 20°C.
Charging and temperature conditions are as follows: at 25°C, the float charging voltage is 13.5 to 13.8 Vdc/battery, and the equalization charging voltage is 14.4 to 15.0 Vdc/battery. The nominal operating temperature is 25°C; discharge is allowed from -15°C to 50°C, and charging and storage are allowed from -15°C to 40°C. For self-discharge, after 90 days in a 25°C environment, capacity loss is less than 10%; it can be stored for up to 6 months and should be fully charged before use; when storage temperature exceeds 25°C, it must be recharged earlier.
The product is manufactured in accordance with IEC 61056-1/2:2012 and has obtained UL1989 Recognized (MH14533). With its pure lead construction and high-rate discharge capability, it is suitable for float service scenarios such as data center UPS that require fast-discharge backup.