Product Features

  • VRLA (Valve Regulated Lead Acid) battery
  • Maintenance-free, with AGM (Absorbent Glass Mat) technology, gas recombination efficiency up to 99%
  • Pure lead construction with proprietary elements
  • Designed for high-rate UPS and float/standby power applications
  • Manufactured in accordance with IEC 60896-21/22:2004 and recognized under UL1989 (MH14533)

Application Scenarios

  • Long-duration backup via front terminals, used in data centers
  • UPS backup batteries supporting high-rate discharge
  • Front-access wiring provides backup power for large equipment rooms
  • Long-duration backup power for telecom equipment rooms
  • High-rate backup for industrial control
  • Uninterruptible power supply for network equipment

Product parameters

  • Model:XPL9000FT
  • Voltage:12 Vdc
  • Nominal Capacity:9000W @5min-rate
  • Watts per Cell:2069.83 (30-Sec 1.67 VPC @ 25°C)
  • Watts per Cell:1403.33 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:907.67 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:75.00 A
  • Max. Discharge Current:1900 A
  • Short Circuit Current:5102 A
  • Internal Resistance:1.86 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
  • Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:69.50 / 153.22 kg / lb.
  • Length (L):558.0±2.5 / 21.97±0.10 mm / in
  • Width (W):126.0±1.5 / 4.96±0.06 mm / in
  • Height (H):323.0±2.5 / 12.72±0.10 mm / in
  • Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

XPL9000FT is a 12V front terminal pure lead valve-regulated sealed lead-acid battery in the CSB XPL-FT series. It is maintenance-free, uses absorbent glass mat (AGM) technology, and can achieve gas recombination efficiency of up to 99%. The series targets high-rate UPS and data center backup power applications, is manufactured according to IEC 60896-21/22:2004, and is recognized under UL1989 (MH14533). Under standby float service at 25°C, its design life can reach 10 years and meets the Eurobat long life standard (greater than 12 years at 20°C); with its pure lead construction and front terminal design, the XPL9000FT is suitable for high-rate backup applications such as data center uninterruptible power supplies, providing reliable backup power support for critical equipment. From a construction perspective, the XPL9000FT uses a PP case (UL 94-HB); a flame-retardant (94-V0) version can also be supplied upon customer request. The terminals are I2 threaded lead alloy terminals that accept M6 bolts, with a recommended torque of 51.7±10.3 Kgf∙cm / 44.9±9.0 Lbf∙in / 5.1±1.0 N∙m. It weighs 69.50 kg (153.22 lb), and its dimensions are 558.0±2.5 mm long, 126.0±1.5 mm wide, and 323.0±2.5 mm high. Electrical specifications: nominal voltage is 12 Vdc, and nominal capacity reaches 9000W @5min-rate (9.60V per PCS @ 25°C). Power per cell is: 2069.83 W/cell at 30 seconds and 1.67 VPC; 1403.33 W/cell at 5 minutes and 1.67 VPC; 907.67 W/cell at 15 minutes and 1.67 VPC. Maximum charge current is 75.00 A, maximum discharge current is 1900 A, short-circuit current is 5102 A, and internal resistance is 1.86 mΩ. Charging and temperature parameters are as follows: at 25°C, float voltage is 13.5 - 13.8 Vdc/battery, and equalize voltage is 14.4 - 15.0 Vdc/battery. The operating temperature range includes nominal 25°C; discharge -15°C to 50°C; charging and storage -15°C to 40°C. For self-discharge, less than 10% after 90 days at 25°C; maximum storage is 6 months, or up to 10 months with equalizing charge. It must be fully charged before being put into service; if the storage temperature exceeds 25°C, it must be charged earlier.