CSB XPL8000FT 12V Valve-Regulated Sealed Lead-Acid Front Terminal Battery
For data center UPS and other applications requiring high-rate float backup power, the CSB XPL8000FT battery belongs to the XPL-FT series and features a 12V front terminal valve-regulated sealed lead-acid construction. The product uses pure lead and AGM technology, delivers 8000W at the 5-minute rate, and has a design float service life of up to 10 years.
Taobao store
WeChat procurement
Product Features
- Battery type is VRLA (valve-regulated lead-acid)
- No routine maintenance required; AGM absorbent glass mat technology enables gas recombination efficiency of up to 99%
- Pure lead construction combined with proprietary elements
- It is specifically designed for high-rate UPS and float standby power applications
- The product is UL1989 recognized (MH14533), and production follows IEC 60896-21/22:2004
Application Scenarios
- Long-duration backup applications, data centers with front terminals
- UPS backup battery with high-rate discharge characteristics
- For backup power requirements, large equipment rooms choose front terminal connections
- Long-duration backup power for telecom equipment rooms
- High-rate backup for industrial control
- Uninterruptible power supply, compatible with network equipment
Product parameters
- Model:XPL8000FT
- Voltage:12 Vdc
- Nominal Capacity:8000W @5min-rate
- Watts per Cell:1831.17 (30-Sec 1.67 VPC @ 25°C)
- Watts per Cell:1287.17 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:821.50 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:66.70 A
- Max. Discharge Current:1660 A
- Short Circuit Current:4570 A
- Internal Resistance:2.17 mΩ
- Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
- Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
- Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:65.30 / 143.96 kg / lb.
- Length (L):558.0±2.5 / 21.97±0.10 mm / in
- Width (W):126.0±1.5 / 4.96±0.06 mm / in
- Height (H):323.0±2.5 / 12.72±0.10 mm / in
- Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
CSB XPL8000FT is a member of the XPL-FT series and is rated as a 12V front terminal valve-regulated sealed lead-acid battery. Absorbent Glass Mat (AGM) technology is used, with gas recombination efficiency up to 99%; a pure lead construction and proprietary formulation are also used. High-rate UPS and data center backup power are the target applications for this series, and the product is classified as a front terminal pure lead VRLA battery; the officially designated application is data center uninterruptible power supply.
In terms of power data, 9.60V per PCS, 25°C, and 8000W at the 5-minute rate are used to indicate the nominal capacity of the XPL8000FT. For cell power: at 25°C and 1.67 VPC, 30 seconds is 1831.17 W/cell, 5 minutes is 1287.17 W/cell, and 15 minutes is 821.50 W/cell. Current and internal resistance data include: maximum charge current 66.70 A, maximum discharge current 1660 A, short-circuit current 4570 A, and internal resistance 2.17 mΩ.
Length 558.0±2.5 mm, width 126.0±1.5 mm, and height 323.0±2.5 mm make up its dimensions, with a total weight of 65.30 kg. The I2 threaded lead alloy terminal can be fitted with an M6 bolt; torque values are 51.7±10.3 Kgf∙cm, 44.9±9.0 Lbf∙in, or 5.1±1.0 N∙m. PP is the case material (UL 94-HB); a flame-retardant 94-V0 version is also available upon request.
Charging and temperature conditions are as follows: at 25°C, float voltage is 13.5 to 13.8 Vdc/battery and equalization voltage is 14.4 to 15.0 Vdc/battery. Nominal operating temperature is 25°C; the discharge range is -15°C to 50°C, and the charging and storage range is -15°C to 40°C. Self-discharge over 90 days (25°C) is less than 10%; it can be stored for 6 months, or up to 10 months with equalization charging. It should be fully charged before use; if storage temperature is above 25°C, charging must be carried out sooner.
For design life: under float standby service at 25°C, life can reach 10 years; under Eurobat 20°C conditions, it is greater than 12 years, falling into the Very Long Life category. The manufacturing standard is IEC 60896-21/22:2004, and it is UL1989 Recognized (MH14533). The front terminal construction and maintenance-free design make installation and maintenance in cabinets or battery racks more convenient; it is suitable for float standby power applications such as data center UPS.