Product Features

  • VRLA (valve-regulated lead-acid) battery
  • Maintenance-free; using AGM (absorbent glass mat) technology, gas recombination efficiency can reach 99%
  • Pure lead construction incorporating proprietary elements
  • Developed for high-rate UPS and float standby power applications
  • Manufactured in accordance with IEC 60896-21/22:2004 and certified to UL1989 (MH14533)

Application Scenarios

  • Data center front-terminal UPS backup
  • Telecom room high-rate discharge backup
  • Rack-mounted UPS rapid-discharge battery
  • Edge data center emergency power
  • Front-access wiring cabinet backup power retrofit
  • Industrial control cabinet UPS backup

Product parameters

  • Model:XHRL12900WFTFR
  • Voltage:12 Vdc
  • Nominal Capacity:900W @ 15min-rate
  • Watts per Cell:2069.83 (30-Sec 1.67 VPC @ 25°C)
  • Watts per Cell:1403.33 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:907.67 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:90.00 A
  • Max. Discharge Current:1900 (5sec)
  • Short Circuit Current:5102 A
  • Internal Resistance:1.86 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
  • Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:69.50 / 153.22 kg / lb.
  • Length (L):558.0±2.5 / 21.97±0.10 mm / in
  • Width (W):126.0±1.5 / 4.96±0.06 mm / in
  • Height (H):323.0±2.5 / 12.72±0.10 mm / in
  • Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): 12+ years, Very Long Life
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

CSB XHRL12900WFTFR is based on the XHRL-FT series platform, rated 12V, and is a front-terminal valve-regulated sealed lead-acid battery; its AGM approach uses absorbent glass mat separators, with gas recombination efficiency up to 99%, and requires no water replenishment during use. The front terminal layout makes front wiring and routine maintenance in cabinets more convenient, and it is intended for high-rate float standby applications such as data center UPS. In terms of dimensions, the battery is 558.0±2.5 mm long, 126.0±1.5 mm wide, and 323.0±2.5 mm high, with a weight of 69.50 kg; the terminal is I2 thread lead alloy terminal, compatible with M6 bolts, torque 51.7±10.3 Kgf∙cm, equivalent to 44.9±9.0 Lbf∙in or 5.1±1.0 N∙m. The case uses PP (UL 94-HB); a flame-retardant (94-V0) version can also be provided if required. Nominal capacity is 900W @ 15min-rate, 10.02V per PCS @ 25°C. For per-cell output, at 1.67 VPC @ 25°C: 2069.83 W/cell at 30 seconds, 1403.33 W/cell at 5 minutes, and 907.67 W/cell at 15 minutes. Current parameters include maximum charge current 90.00 A, 5-second maximum discharge current 1900 A, short-circuit current 5102 A, and internal resistance 1.86 mΩ. Charging and temperature conditions: float charge voltage at 25°C is 13.5 to 13.8 Vdc/battery, equalization voltage 14.4 to 15.0 Vdc/battery; nominal temperature is 25°C, discharge range is -15°C to 50°C, and charging and storage range is -15°C to 40°C. Under float standby service at 25°C, design life can reach 10 years; the Eurobat (20°C) standard is over 12 years, Very Long Life. Regarding self-discharge, it is less than 10% after 90 days on shelf; it can be stored for 6 months at 25°C, extended to 10 months with equalizing charge. It should be fully charged before being put into service; if storage temperature is above 25°C, charge earlier. The product uses pure lead construction and proprietary elements, is manufactured to IEC 60896-21/22:2004, and is UL1989 Recognized (MH14533). These features make it suitable for high-rate discharge and float standby applications such as data center UPS.
link
Go to purchase
Telephone
13775032303
email
powercube@foxmail.com
wechat
wechat
Loading...