CSB XHRL12800WFTFR 12V Valve-Regulated Sealed Lead-Acid Front Terminal Battery
Designed for high-rate float standby requirements such as data center UPS, the CSB XHRL12800WFTFR uses AGM technology and is a 12V front terminal valve-regulated sealed lead-acid battery. Its nominal capacity is 800W @ 15min-rate, with a design life of up to 10 years.
Taobao store
WeChat procurement
Product Features
- Battery type is classified as VRLA (valve-regulated lead-acid)
- Maintenance-free; gas recombination efficiency can reach up to 99%, relying on AGM absorbent glass mat technology
- Constructed from pure lead with proprietary elements
- Developed for float standby power and high-rate UPS applications
- Manufactured to IEC 60896-21/22:2004 and recognized under UL1989 (MH14533)
Application Scenarios
- Front-terminal UPS backup for data centers
- High-rate discharge backup for telecom rooms
- Fast-discharge battery for rack-mounted UPS
- Emergency power for edge data centers
- Backup power retrofit for front-access wiring cabinets
- UPS backup for industrial control cabinets
Product parameters
- Model:XHRL12800WFTFR
- Voltage:12 Vdc
- Nominal Capacity:800W @ 15min-rate
- Watts per Cell:1831.17 (30-Sec 1.67 VPC @ 25°C)
- Watts per Cell:1287.17 (5-Min 1.67 VPC @ 25°)
- Watts per Cell:821.50 (15-Min 1.67 VPC @ 25°)
- Max. Charge Current:80.00 A
- Max. Discharge Current:1660 (5sec)
- Short Circuit Current:4570 A
- Internal Resistance:2.17 mΩ
- Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
- Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
- Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
- Weight:65.30 / 143.96 kg / lb.
- Length (L):558.0±2.5 / 21.97±0.10 mm / in
- Width (W):126.0±1.5 / 4.96±0.06 mm / in
- Height (H):323.0±2.5 / 12.72±0.10 mm / in
- Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): 12+ years, Very Long Life
- Float Charging Voltage:13.5 - 13.8 Vdc/battery
- Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
- Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
Product details
CSB XHRL12800WFTFR belongs to the XHRL-FT series, meets IEC 60896-21/22:2004, and is UL1989 recognized (MH14533). Its pure lead construction combined with proprietary elements is designed for high-rate UPS float standby power. This product is a 12V front terminal valve-regulated sealed lead-acid battery, using absorbent glass mat (AGM) technology, with gas recombination efficiency up to 99%, maintenance-free; front terminals make front-of-cabinet wiring more convenient, so it is often used in data center UPS (uninterruptible power supply) and other applications requiring high-rate float backup.
Electrical: 12 Vdc is the nominal voltage; at 15min-rate, nominal capacity is 800W (10.02V per PCS @ 25°C). At 25°C and 1.67 VPC, output is 1831.17 W/cell for 30 seconds, 1287.17 W/cell for 5 minutes, and 821.50 W/cell for 15 minutes. Maximum charge current 80.00 A; maximum discharge current for 5 seconds 1660 A; short-circuit current 4570 A; internal resistance 2.17 mΩ.
Dimensions: 558.0±2.5 mm (L) × 126.0±1.5 mm (W) × 323.0±2.5 mm (H), weight approx. 65.30 kg. I2 threaded lead alloy terminals accept M6 bolts; recommended torque 51.7±10.3 Kgf∙cm (44.9±9.0 Lbf∙in or 5.1±1.0 N∙m). The case is PP (UL 94-HB); a 94-V0 flame-retardant version can be provided on request.
When the ambient is 25°C and in float charge state, the battery design life can reach 10 years; measured according to Eurobat (20°C), it can exceed 12 years, corresponding to Very Long Life. At 25°C, the float voltage range is 13.5-13.8 Vdc/battery, and the equalization voltage range is 14.4-15.0 Vdc/battery. Temperature ranges include: nominal 25°C; discharge from -15°C to 50°C; charge/storage from -15°C to 40°C. In a 25°C environment after 90 days, the self-discharge rate remains below 10%; it can be stored for 6 months, and if equalization charging is performed once every 10 months, the storage period can be further extended. It must be fully charged before use; if storage temperature exceeds 25°C, charge earlier.