Product Features

  • Battery using valve-regulated sealed lead-acid (VRLA) technology
  • Maintenance-free, with absorbent glass mat (AGM) technology, gas recombination efficiency up to 99%
  • Utilizes pure lead construction with proprietary elements
  • Purpose-built for high-rate UPS and float-charge standby power applications
  • Manufactured to IEC 61056-1/2:2012 standards, UL1989 recognized (MH14533)

Application Scenarios

  • Data center UPS backup battery
  • Server room uninterruptible power supply
  • Industrial UPS high-power backup
  • Medical equipment UPS emergency power supply
  • Financial system UPS backup
  • Telecommunications room UPS backup

Product parameters

  • Model:UPS122406
  • Voltage:12 Vdc
  • Nominal Capacity:240W @5min-rate
  • Watts per Cell:38.83 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:18.5 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:2.00 A
  • Max. Discharge Current:130 A
  • Short Circuit Current:230 A
  • Internal Resistance:33.50 mΩ
  • Terminal Type:F2 terminal (Faston Tab 250)
  • Container Material:ABS (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:1.46 / 3.22 kg / lb.
  • Length (L):150.9±2.0 / 5.94±0.08 mm / in
  • Width (W):51.0±1.0 / 2.01±0.04 mm / in
  • Height (H):98.6±1.0 / 3.88±0.04 mm / in
  • Design Life:Up to 5 years in standby service at 25°C; Eurobat (20°C): 3-5 years, Standard Commercial
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C
  • Note:F1 terminal is available; Max Discharge Current = 100 A (5 sec.)

Product details

For applications such as data center UPS requiring high-rate discharge and float standby, the CSB UPS122406 comes from the UPS series, a line of 6V and 12V top-terminal valve-regulated sealed lead-acid (VRLA) batteries. It uses absorbent glass mat (AGM) technology, can achieve up to 99% gas recombination efficiency, and is maintenance-free; the series uses pure lead construction and is designed for uninterruptible power supply (UPS) high-rate discharge and float standby requirements, with official applications in data center UPS. Structurally, the terminal type is F2 terminal - Faston Tab 250; the case material is ABS (UL 94-HB), and a flame-retardant (94-V0) version is available on request. Dimensions are 150.9±2.0 mm long, 51.0±1.0 mm wide, and 98.6±1.0 mm high, with a weight of approximately 1.46 kg. Under float standby service at 25°C, design life can reach 5 years; according to Eurobat (20°C), commercial life is 3 to 5 years. Nominal temperature is 25°C (77°F), discharge temperature is -15°C to 50°C (5°F to 122°F), and charging and storage temperature is -15°C to 40°C (5°F to 104°F). Electrical specifications: UPS122406 rated voltage is 12 Vdc; nominal capacity is calculated at 9.60V per PCS @ 25°C, 240W @5min-rate. Power per cell: 38.83 W/cell at 1.67 VPC @ 25°C for 5 minutes, 18.5 W/cell at 1.67 VPC @ 25°C for 15 minutes. Maximum charge current 2.00 A, maximum discharge current 130 A, short-circuit current 230 A, internal resistance 33.50 mΩ. Float voltage 13.5 to 13.8 Vdc/battery (25°C), equalization voltage 14.4 to 15.0 Vdc/battery (25°C). Self-discharge: after 90 days of storage at 25°C (77°F), self-discharge is less than 10%, and it can be stored for up to 6 months; fully charge before use, and charge earlier if storage temperature is above 25°C (77°F). The product complies with IEC 61056-1/2:2012 and is UL1989 recognized (MH14533). Therefore, it is suitable for data center UPS and other applications requiring high-rate discharge and float standby.