Product Features

  • VRLA (valve-regulated lead-acid) battery
  • No routine maintenance required; with AGM (absorbent glass mat) technology, gas recombination efficiency up to 99%
  • Construction uses pure lead and includes proprietary elements
  • Designed for float/standby power applications
  • Manufacturing process follows IEC 60896-21/22:2004; UL Recognized under UL1989 (MH14533)

Application Scenarios

  • Backup power application: broadband access network equipment room
  • Standby power application: fiber-to-the-home central office
  • DC power application: telecom outdoor cabinet
  • Multi-hour backup power application: telecom base station
  • Backup power application: cable TV network node
  • Power application: broadband integrated services access point

Product parameters

  • Model:TPL122000FR
  • Voltage:12 Vdc
  • Nominal Capacity:200 Ah @10hr-rate
  • Ah Capacity:198 (8-Hr 1.75 VPC @ 25°C)
  • Ah Capacity:214 (20-Hr 1.75 VPC @ 25°C)
  • Ah Capacity:194 (8-Hr 1.80 VPC @ 25°C)
  • Max. Charge Current:60.0 A
  • Max. Discharge Current:1150 A
  • Short Circuit Current:3093 A
  • Internal Resistance:3.60 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
  • Container Material:Flame-retardant ABS (UL 94-V0)
  • Weight:59.70 / 131.58 kg / lb.
  • Length (L):560.0±2.5 / 22.05±0.10 mm / in
  • Width (W):124.0±1.5 / 4.88±0.06 mm / in
  • Height (H):323.0±2.5 / 12.72±0.10 mm / in
  • Design Life:Up to 12 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

As a member of the CSB TPL series, the TPL122000FR uses a valve regulated sealed lead acid construction and is a 12V front terminal battery; it features a pure lead construction and AGM technology, with a gas recombination efficiency of up to 99%, and requires no maintenance during use. This model is positioned as a long-life pure lead front terminal battery for the telecommunications sector, suitable for broadband applications requiring several hours of backup power. According to official specifications, its application is telecommunications, primarily serving as a float standby power source. Capacity data is as follows: at 25°C, with 1.80VPC as the end condition, the nominal capacity at the 10-hour rate is 200Ah; at the same temperature, 1.75VPC at the 8-hour rate is 198Ah, 1.75VPC at the 20-hour rate is 214Ah, and 1.80VPC at the 8-hour rate is 194Ah. Maximum charge current is 60.0A, maximum discharge current is 1150A, short-circuit current is 3093A, and internal resistance is 3.60mΩ. At 25°C, float voltage range is 13.5 to 13.8Vdc/battery, and equalization voltage range is 14.4 to 15.0Vdc/battery. In terms of dimensions, length, width, and height are 560.0±2.5mm, 124.0±1.5mm, and 323.0±2.5mm respectively, with an overall weight of 59.70kg. Terminals are of the I2 threaded lead alloy type and can be installed with M6 bolts; recommended torque is 51.7±10.3Kgf·cm, which converts to 44.9±9.0Lbf·in, that is, 5.1±1.0N·m. The case uses flame-retardant ABS material and meets UL 94-V0 requirements. Temperature conditions: nominal temperature 25°C; discharge permitted from -15°C to 50°C; charging and storage permitted from -15°C to 40°C. After standing at 25°C for 90 days, self-discharge is below 10%; it can be stored at 25°C for up to 6 months, and should be fully charged before being put into service. When storage temperature exceeds 25°C, the supplementary charge interval must be shortened. In terms of design life, it can reach 12 years under 25°C float charging, meeting the Eurobat long life standard; at 20°C it exceeds 12 years and is classified as very long life. Manufacturing is based on IEC 60896-21/22:2004, and it is UL1989 recognized (MH14533). The front terminal layout makes wiring and maintenance in cabinets or battery racks more convenient, making it suitable for float standby power applications such as telecommunications that require longer backup times.