Product Features

  • The battery is of the valve-regulated lead-acid (VRLA) type
  • With AGM (absorbent glass mat) technology, gas recombination efficiency can reach up to 99%, and requires no maintenance
  • The construction uses pure lead with proprietary elements
  • Designed for float standby power applications
  • The manufacturing process complies with IEC 60896-21/22:2004 and has obtained UL1989 recognition (MH14533)

Application Scenarios

  • Backup application: broadband access network equipment room
  • Standby power use: fiber-to-the-home central office
  • DC power supply scenario: telecom outdoor cabinet
  • Long-duration backup: communication base station
  • Backup scenario: cable TV network node
  • Power support: broadband integrated service access point

Product parameters

  • Model:TPL121800FR
  • Voltage:12 Vdc
  • Nominal Capacity:180 Ah @10hr-rate
  • Ah Capacity:175 (8-Hr 1.75 VPC @ 25°C)
  • Ah Capacity:192 (20-Hr 1.75 VPC @ 25°C)
  • Ah Capacity:172 (8-Hr 1.80 VPC @ 25°C)
  • Max. Charge Current:54 A
  • Max. Discharge Current:800 A
  • Short Circuit Current:2575 A
  • Internal Resistance:3.90 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
  • Container Material:Flame-retardant ABS (UL 94-V0)
  • Weight:55.1 / 121.44 kg / lb.
  • Length (L):547.0±2.5 / 21.54±0.10 mm / in
  • Width (W):124.8±1.5 / 4.94±0.06 mm / in
  • Height (H):320.3±2.5 / 12.72±0.10 mm / in
  • Design Life:Up to 12 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

The CSB TPL121800FR is positioned for float standby power and can be used in telecommunications, meeting multi-hour backup power requirements in broadband applications; it is manufactured in accordance with IEC 60896-21/22:2004 and has obtained UL1989 recognition (MH14533). Because it is a VRLA battery, it is maintenance-free and can be flexibly deployed in a variety of backup power systems. Its case uses flame-retardant ABS (UL 94-V0). The terminal specification is an I2 threaded lead alloy terminal, compatible with M6 bolts, with a recommended torque of 51.7±10.3 Kgf·cm (44.9±9.0 Lbf·in or 5.1±1.0 N·m). Dimensions: length 547.0±2.5 mm, width 124.8±1.5 mm, height 320.3±2.5 mm; weight approximately 55.1 kg (121.44 lb). Thanks to the front terminal layout, rack installation and maintenance are more convenient. Electrical parameters are as follows: maximum charge current 54 A, maximum discharge current 800 A, short-circuit current 2575 A, internal resistance 3.90 mΩ. At 25°C, float voltage is 13.5 to 13.8 Vdc/battery, and equalization voltage is 14.4 to 15.0 Vdc/battery. At the same temperature, self-discharge after 90 days on shelf is less than 10%; it can be stored for up to 6 months and should be fully charged before being put into service; if the storage temperature exceeds 25°C, charging should be brought forward accordingly. Temperature range: nominal 25°C; discharge -15°C to 50°C; charge and storage -15°C to 40°C. Capacity: at 1.80 VPC and 25°C, nominal capacity is 180 Ah at the 10-hour rate; at 1.75 VPC, 175 Ah at the 8-hour rate and 192 Ah at the 20-hour rate; at 1.80 VPC, 172 Ah at the 8-hour rate. When operated in standby service at 25°C, design float life is up to 12 years; it meets the Eurobat long life standard, greater than 12 years at 20°C. As a member of the TPL series, this battery is a front terminal VRLA battery. Its construction is based on pure lead and a proprietary formula, and uses absorbed glass mat (AGM) technology, with gas recombination efficiency up to 99%. Nominal voltage 12 Vdc.