Product Features

  • The battery uses a valve-regulated lead-acid (VRLA) type
  • Based on AGM (Absorbent Glass Mat) technology, maintenance-free, with gas recombination efficiency up to 99%
  • Internal pure lead construction with proprietary elements added
  • Specifically designed for high-rate UPS and float standby power applications
  • Production is in accordance with IEC 60896-21/22:2004, and UL1989 recognition (MH14533) has also been obtained

Application Scenarios

  • UPS backup scenario: hyperscale data center
  • Standby power application: high-performance computing center
  • UPS application: cloud computing data center
  • Uninterruptible power supply protection: financial data center
  • High-rate discharge standby requirement: communications hub
  • High-power backup application: industrial-grade UPS

Product parameters

  • Model:XHRL12250W
  • Voltage:12 Vdc
  • Nominal Capacity:250W @15min-rate
  • Watts per Cell:463.17 (5-Min 1.67 VPC @ 25°)
  • Watts per Cell:252.67 (15-Min 1.67 VPC @ 25°)
  • Max. Charge Current:25.00 A
  • Max. Discharge Current:650 A
  • Short Circuit Current:1680 A
  • Internal Resistance:4.20 mΩ
  • Terminal Type:I2 thread lead alloy terminal to accept M6 bolt
  • Terminal Torque:51.7±10.3 Kgf·cm / 44.9±9.0 Lbf·in / 5.1±1.0 N·m
  • Container Material:PP (UL 94-HB) standard, flame-retardant (94-V0) available upon request
  • Weight:18.52 / 40.82 kg / lb.
  • Length (L):228.0±2.5 / 8.98±0.10 mm / in
  • Width (W):138.4±1.5 / 5.45±0.06 mm / in
  • Height (H):206.3±2.5 / 8.12±0.10 mm / in
  • Design Life:Up to 10 years in standby service at 25°C; Eurobat (20°C): >12 years, Very Long Life
  • Float Charging Voltage:13.5 - 13.8 Vdc/battery
  • Equalizing Charging Voltage:14.4 - 15.0 Vdc/battery
  • Operating Temperature:discharge -15°C to 50°C; charge/storage -15°C to 40°C

Product details

CSB XHRL12250W is primarily designed for data center uninterruptible power supplies and is suitable for high-rate discharge, float standby, and similar applications; it is a 12V valve-regulated sealed lead-acid battery in the XHRL series. As a high-performance variant of HRL, the XHRL series is aimed at UPS and data center requirements and can deliver higher high-rate output. This battery uses Absorbent Glass Mat (AGM) technology, achieves gas recombination efficiency of up to 99%, features a maintenance-free design, and uses pure lead construction with proprietary elements. Its official application area is data center uninterruptible power supplies. When operated in float standby service at 25°C, this battery can achieve a design life of 10 years; according to the Eurobat standard (20°C), it falls into the very long life class of greater than 12 years. Regarding temperature conditions, the nominal temperature is 25°C; discharge is allowed from -15°C to 50°C, and charging/storage is allowed from -15°C to 40°C. After 90 days of storage in a 25°C environment, the self-discharge rate is less than 10%; it can be stored for up to 6 months, and must be fully charged before being put into operation; when storage temperature exceeds 25°C, recharge should be done in advance. The battery is manufactured in accordance with IEC 60896-21/22:2004 and is recognized under UL1989 (MH14533). In terms of electrical specifications, the nominal voltage is 12 Vdc, and the nominal capacity is 250W (15-minute rate, 1.67 VPC @25°C). The 5-minute rate power is 463.17 W/cell; the 15-minute rate power is 252.67 W/cell (1.67 VPC @25°C). The maximum charge current is 25.00 A, and the maximum discharge current is 650 A; the short-circuit current is 1680 A, and the internal resistance is 4.20 mΩ. At 25°C, the float charge voltage is 13.5 - 13.8 Vdc/battery, and the equalization charge voltage is 14.4 - 15.0 Vdc/battery. For terminals, the XHRL12250W uses I2 threaded lead-alloy terminals, accepts M6 bolts, and the terminal torque is 51.7±10.3 Kgf∙cm or 44.9±9.0 Lbf∙in or 5.1±1.0 N∙m. The case material is PP (UL 94-HB); a flame-retardant version (94-V0) is available upon request. The weight is 18.52 kg (40.82 lb), and dimensions are length 228.0±2.5 mm, width 138.4±1.5 mm, and height 206.3±2.5 mm. With its high-rate discharge capability, it can be used in applications requiring reliable backup power, such as data center UPS, and meets the requirements of float service standby applications.